Offers & Rollbacks Low prices on 100's of items

Welcome to our store. Learn more

Direct EU Shipping | Fast Dispatch Across Europe

TWO POLE VOLTAGE TESTER WITH RCD TEST (YT-28330)

€6739
Tax included, shipping calculated at checkout.

Description

YT-28330
TWO POLE VOLTAGE TESTER WITH RCD TEST
Brand
Yato
Entity responsible for this product in the EU
TOYA S.A.More
Series
GRF
Alternating voltage
6-1000 V a.c.
Direct voltage
6-1000 V d.c.
Resistance
0-1999
Frequency
50-400 Hz
Continuity test
0-400 M
Phase sequence test
yes
Voltage detection
yes, automatic
Polarity detection
yes, full range
Measurement accuracy
(3% + 5)
Reaction time
<1 (LED indicators), 1 (LCD display) s
Dimensions
280x74x34 mm
Display type
LCD
Display resolution
1 V a.c./V d.c.
Display range
1999
LED display thresholds
12, 24, 50, 120, 230, 400, 690, 1000 V a.c./V d.c.
Auto measurement range
yes
RCD tripping
~30 mA / 230 V
Max. measurement duration
30 s
Recovery time (time between two RCD tests)
240 s
Low impedance voltage test mode
yes, approximately 7 k (to eliminate noise)
Peak current Is (load)
150 mA
Impedance / peak current
350 k / Is <3.5 mA (does not trip RCD)
Bell ring
yes
Automatic start-up
12 V a.c./V d.c. (LED indicators), 6 V a.c./V d.c. (LCD display)
Power supply
energy source
cell type
2x1.5V; AAA
Working temperature range
-10 ~ +50 C
Operating relative humidity Rh
<85%
Storage temperature
-10 ~ +50 C
Protection grade
IP64
Weight
285 g
Application
electric
Symbol
YT-28330

Bipolar voltage tester in a solid housing with flexible cables in silicone insulation. Detects and measures AC and DC voltages in the range of 6 to 1000 V. The result is indicated on the LCD display and via LED indicators. The tester also allows you to:

check the phase rotation sequence in three-phase systems
check the voltage in low impedance mode (to eliminate noise)
test the operation of RCD switches with a rated current of 30 mA or less
perform circuit continuity test and measure resistance up to 1999 ohms
Measurements in low light conditions are facilitated by the built-in LED flashlight. Measurement safety is supported by a solid and sealed housing with IP64 standard. The set includes screw-on probe caps to facilitate measurements in sockets. The meter meets the requirements of CAT III 1000 V / CAT IV 600 V surge protection categories.

DC voltage measurement: 6-1000 V d.c.
AC voltage measurement: 6-1000 V a.c.
Resistance measurement: 0-1999
Frequency measurement: 50-400 Hz
Circuit continuity test: 0-400 M
Measurement accuracy: (3% + 5)
Impedance (peak current): 350 k / Is <3.5 mA (does not trigger RCD)
Response ti